FCS-LWM-1 Installation_Guide.pdf

(2733 KB) Pobierz
Linear Heat Detector
FCS-LWM-1
en
Installation note
Linear Heat Detector
Table of Contents | en
3
Table of Contents
1
Safety Instructions
4
2
Short Information
4
3
System Overview
5
4
4.1
4.2
4.3
Installation
Linear Installation
Area Installation
Installation in Ex-zones
6
6
7
10
5
5.1
5.2
5.3
Connection
Connecting Sensor Cables
Connecting the Control Unit to the Fire Panel
Wiring Diagram
10
10
12
12
6
6.1
6.2
6.3
Configuration
Switch Positions
Setting the Response Temperature (MAX ALARM)
Setting the Response Temperature Dependent on Time (DIFF ALARM/DIFF TIME)
13
14
14
16
7
7.1
7.2
Technical Data
Electrics
Mechanics
18
18
18
Bosch Sicherheitssysteme GmbH
Installation note
F.01U.028.512 | 3.0 | 2010.11
4
en | Safety Instructions
Linear Heat Detector
1
Safety Instructions
CAUTION!
Product components can become damaged by electrostatic discharge.
Wear a grounding wrist strap if you are working on the open PCB.
CAUTION!
Do not connect the grounding drain wire to grounding clips 3–4, because connection to the
grounding drain wire will raise a fault message to the BZ 500 and UEZ 2000 fire panels.
NOTICE!
The FCS-LWM-1 Heat Detector is intended for use with the DIN EN 54-5:2000 response grades
A1, A2, B, and C.
NOTICE!
The FCS-LWM-1 Heat Detector can be used in explosive zones 1, 2, 21, and 22. For notes on
installation in ex-zones, see
Page 10.
NOTICE!
The maximum monitoring height is 7.5 m. For rooms with higher ceilings a special VdS
authorization is required.
NOTICE!
Have maintenance and installation work carried out regularly by trained, qualified personnel
only. Bosch Security Systems recommends a functional and visual inspection once a year.
NOTICE!
Unusable electronic devices may not be disposed of with the household garbage, but rather in
accordance with the applicable regulations and directives (e.g. WEEE).
2
Short Information
FCS-LWM-1 is a linear heat detector for detecting fire. It is suitable for use in constricted
spaces and under extreme environmental conditions. The control unit reports temperature
differences by monitoring the resistance in the sensor cable. If the temperature rises, the
electrical resistance falls and the control unit outputs an alarm message depending on the
response temperature.
The response temperature for the MAX ALARM is set using a 16-position switch. If the
response temperature is exceeded, an alarm message is output. The differential alarm
threshold for the DIFF ALARM is set using two 16-position switches
DIFF TIME and
DIFF ALARM.
Located on the control unit are four LEDs, which display the status. The green LED signals
normal mode, the yellow LED a fault and the two red LEDs signal MAX ALARM and DIFF
ALARM.
F.01U.028.512 | 3.0 | 2010.11
Installation note
Bosch Sicherheitssysteme GmbH
Linear Heat Detector
System Overview | en
5
The control unit features three keys. The two test keys TEST FAULT and TEST ALARM can be
used to test the system for fault or alarm. The RESET key restores the system to its original
status.
3
System Overview
27
29
28
20
21
22
23
24
11
12
ON ECE
1
ON ECE
ON ECE
2 3
4
1
2 3
4
1
2 3
4
25
13
14
1
2
3
4
5
6
7
8
9
10
LWM 1
1
ON ECE
26
15
16
17
18
19
2 3
4
Figure 3.1
No.
1
2
3+4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20+21
22
23
24
25
Designation
PWR-
IN+
Assignment
Supply voltage
Supply voltage
Grounding clamps (not used)
Orange sensor cable
White sensor cable
Blue sensor cable
Red sensor cable
External reset input
External reset input
Fault relay, normally open
Fault relay, contact made
Fault relay, normally closed
MAX ALARM relay, normally open
MAX ALARM relay, contact made
MAX ALARM, normally closed
DIFF ALARM relay, normally open
DIFF ALARM relay, contact made
DIFF ALARM relay, normally closed
--
MAX ALARM or DIFF ALARM actuate
both relays
Does not transmit fault or alarm
messages to fire panel when "ON"
Calibration switch – time span of
increase in temperature
Calibration switch – response
temperature depending on DIFF TIME
SENSOR OR
SENSOR WH
SENSOR BL
SENSOR RD
EXT. RESET
EXT. RESET
FAULT NO
FAULT CM
FAULT NC
MAX ALARM NO
MAX ALARM CM
MAX ALARM NC
DIFF ALARM NO
DIFF ALARM CM
DIFF ALARM NC
Unused
MAX+DIFF
ISOLATE
DIFF TIME
DIFF ALARM
Bosch Sicherheitssysteme GmbH
Installation note
F.01U.028.512 | 3.0 | 2010.11